Page 40 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083
Complete Check, Test and Start Procedure
Renewable Media
(Single-use and
Permanent Wire
Mesh Filters Also
Available.)
Provide completed Check, Test and Start form to your local AAF
®
-
HermanNelson
®
representative and specifying engineer for verication
that proper start-up was completed.
The form is enclosed in the manila envelope located behind the left
front access door.
Turn off the unit (fan speed switch or unit on/off switch is located
behind the right front end compartment panel). Remove the center
front panel, pull out the lter and replace with a clean lter. Replace
the center panel and restart the unit.
Filters should be replaced during the rst week of placing into service
to prevent dirt carry-over into the internals of the unit and back into the
classroom (see gure 75). A periodic lter changeout program should
be established. Filters should be checked monthly or more often if
conditions indicate. Filters are included in all units.
Filter
Motor
Figure 75: Filter Installation
Installer/Owner’s Responsibility
Protect your investment - read carefully
Your Daikin express written limited warranty does not cover equipment
failures that are caused by misuse, abuse, mis-installation, failure to
maintain the unit, etc. Here are a few examples of the types of damage
not covered by warranty:
1. Damage resulting from handling during transportation or
installation.
2. Damage to compressor resulting from improper electrical phase
hook up.
3. Progressive damage to unit from failure to check and test at start-
up.
4. Damage to electronic or electrical components from incorrect
or uctuating power supply, stray static electricity, or building
automation network inputs.
5. Inaccessibility of unit for service or parts installation that prevents
proper equipment operation.
6. Damage to aluminum coils and electronic controls, etc., resulting
from operating the unit while building maintenance cleaning agents
are in use.
7. Damage resulting from freezing water or condensate, inadequate
or interrupted water supply, use of corrosive water, rearrangement
of unit piping system, fouling or restriction of the water circuit by
foreign material.
8. Damage caused by not cleaning or replacing lters.
9. Damage resulting from failure to keep evaporator coil and intake
clean.
10. Damage caused by accident, alteration of the unit design or
tampering.
Please complete and return the Check, Test and Start document
immediately to protect your warranty.
1. Before proceeding, inspect the fan system, to verify that all parts are
aligned properly and move freely. Inspect fans and fan discharge area
for obstructions. Verify that power has been disconnected. Rotate
the fan assembly manually. Check that a clean lter is installed and
the area in front of unit ventilator is free of debris. All panels should
be in place and properly fastened. Check for outdoor air leaks and
condensation. Verify that the coil section is properly sealed using
the insulating foam donuts supplied.
2. After the unit ventilator has been properly installed, activate unit
electrical power and applicable refrigerant systems
.
3. Using the applicable control, activate the unit ventilator. Depending
on the operating mode selected, the dampers, fans, and other
components should operate as needed.
4. Run the unit ventilator for ten minutes, listening and observing. Fans
should be operating correctly and rotating in the proper direction,
without unusual noise. Likewise, the unit should be free of sheet
metal rattles and / or unusual noises. All panels should be in place
and properly fastened. Check for air leaks and condensation.
Compressor should run without noise. If noisy, check electrical
phases to verify that the compressor is rotating correctly. Phase
reversal can damage the compressor and void the warranty.
Prepare for Start-up
Units must have a lter installed when operating. Operation
without a lter can compromise unit performance due to build
up of dust and dirt on components.
CAUTION
Electric heat units should ONLY use permanent wire mesh lters.
Filters other than wire mesh are not intended for electric heat units,
and can cause unit damage, property damage or personal injury.
CAUTION
Remove debris, dust, dirt, and any obstruction from the area
in front of the return air intake grille at the oor.
CAUTION
Dirty or clogged lters can impact unit performance, and damage
the unit.
CAUTION