IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 19 of 42
Operating Limits
1
At ISO 13256-1 flow rate.
2
Maximum and minimum values may not be combined. If one
value is at maximum or minimum, the other two conditions may
not exceed the normal condition for standard units. Extended range
units may combine any two maximum or minimum conditions, but
not more than two, with all other conditions being normal conditions.
Standard Range Geothermal Range
Units Units
Cooling Heating Cooling Heating
Min. Entering Water
1,2
13°C 13°C -1°C -6°C
Normal Entering Water 29°C 21°C 25°C 4°C
Max Entering Water 43°C 32°C 43°C 32°C
Standard Range Geothermal Range
Units Units
Cooling Heating Cooling Heating
Min. Entering Water
1,2
55°F 55°F 30°F 20°F
Normal Entering Water
85°F 70°F 77°F 40°F
Max Entering Water
110°F 90°F 110°F 90°F
Standard Range Geothermal Range
Units Units
Cooling Heating Cooling Heating
Min. Ambient Air 10°C 10°C 5°C 5°C
Normal Ambient Air 27°C 21°C 27°C 21°C
Max Ambient Air 38°C 29°C 38°C 29°C
Min. Entering Air
1,2
10°C 10°C 10°C 5°C
Normal Entering Air db/wb 27/19°C 21°C 27/19°C 21°C
Max Entering Air db/wb
1,2
38/28°C 27°C 38/28°C 27°C
Standard Range Geothermal Range
Units Units
Cooling Heating Cooling Heating
Min. Ambient Air 50°F 50°F 40°F 40°F
Normal Ambient Air 80°F 70°F 80°F 70°F
Max Ambient Air 100°F 85°F 100°F 85°F
Min. Entering Air
1,2
50°F 50°F 50°F 40°F
Normal Entering Air db/wb 80/67°F 70°F 80/67°F 70°F
Max Entering Air db/wb
1,2
100/83°F 80°F 100/83°F 80°F
Additional Information For Initial
Start-up
Standard Range units
Units are designed to start-up in an ambient of 50°F (10°C), with
entering air at 50°F (10°C), with entering water at 70°F (21°C), with
both air and water ow rates used in the ISO 13256-1 rating test, for
initial start-up in winter.
Note: This is not a normal or continuous operating
condition. It is assumed that such a start-up is for the
purpose of bringing the building space temperature
up to occupancy temperature setpoint.
Geothermal Range units
Geothermal heat pump unit ventilators are designed to start-up in an
ambient of 40°F (5°C), with entering air at 40°F (5°C), with entering
water at 25°F (-4°C), with both air and water at ow rates used in the
ISO 13256-1 rating test, for initial start-up in winter.
Note: This is not a normal or continuous operating
condition. It is assumed that such a start-up is for the
purpose of bringing the building space temperature
up to occupancy temperature setpoint.
Table 6: Air Limits - °F (English units)
Table 8: Water - °F (English units)
Table 7: Air Limits - °C (SI units)
Table 9: Water - °C (SI units)