Page 30 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083
MicroTech II™ Unit Electrical
Connections
To avoid electrical shock, personal injury or death, be sure that eld
wiring complies with local and national re, safety, and electrical
codes, and voltage to the system is within the limits shown in the
job-specic drawings and unit electrical data plate(s).
Power supply to unit must be disconnected before making eld
connections. To avoid electrical shock, personal injury or death,
be sure to rigorously adhere to eld wiring procedures regarding
proper lockout and tagout of components.
See Table 11, 12 & 13, and Figure 47 and the job-specic electrical
drawings before proceeding with eld power and control wiring. See
also the wiring diagram provided on the unit ventilator right front
access panel.
Unit ventilators equipped with an optional electric heating coil have
electric heating coil power connections at right end only.
Procedure
1. Provide power supply to right end compartment to match unit
nameplate.
Figure 48: Electrical Power On/Off Switch Located
Behind Front-Middle Access Panel in Wire Trough, with
Power Entry accessed Behind Right-Front Access Panel
Use copper conductors only. Use of aluminum conductors may
result in equipment failure and overheating hazards. All wiring
in right hand compartment must be class 1.
DANGER
WARNING
CAUTION
2. Conrm that power is de-energized and locked and tagged-out.
3. Plug in the unit control wiring male plug(s) into the appropriate
female plug(s). Refer to Figures 49, 51, 52 & 53.
Plug in 4-pin (for MicroTech II and Electromechanical, see
Figure 51).
10-pin (MicroTech II only, see Figure 52).
12-pin (MicroTech II only, see Figure 53).
4. Insert the main power wires into the main power On/Off switch
terminal lugs (A, B and C). Note that terminal lug B, not used
on single phase. Connect the Ground wire to the ground lug as
shown in Figure 50. Tighten the terminal lugs securely.
5. Reinstall the cover plate on the main power wire trough.
Note: For Electromechanical wiring (see page 36).
Control connections for elecromechanical are made to the
terminal block in the left end compartment.
Figure 49: Control Wiring Plug Connections in Right End
Compartment.
Figure 50: Electrical Power On/Off Switch for Power
Wiring Connections
Grommeted Power Wire Entry
Unit Main Power
On/Off Switch
Terminal lugs for main power wiring from unit,
eld connection by others
B
A
C
Main Power On/Off Switch
Ground Lug
Control wiring whips with
caps located in the right
front end compartment
Note: B not used on single phase.