IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 25 of 42
15. Outdoor Air Temperature Sensor (S3): The sensor is located in the
outdoor air section of the unit before the outdoor air damper. With
network applications, the unit mounted sensor can be overridden
by a remote sensor through the network.
16. Outdoor Air Humidity Sensor (S8) (optional): Unit mounted
humidity sensor for units using Expanded outdoor enthalpy
economizer or Leading Edge indoor/outdoor, true enthalpy
comparison economizer. The sensor is located in the outdoor air
section of the unit before the outdoor air damper. With network
applications, the unit mounted sensor can be overridden by a
remote sensor through the network.
17. Room Humidity Sensor (S6) (optional): Unit mounted humidity
sensor for units capable of active dehumidication or with units
using Leading Edge indoor/outdoor, true enthalpy comparison
economizer. The sensor is located in the sampling chamber (front,
center panel) where room air is continuously drawn through for
fast response to humidity changes in the room. With network
applications, the unit mounted sensor can be overridden by a
remote sensor through the network.
18. CO2 Sensor (S7) (optional): Unit mounted, single beam absorption
infrared gas sensor with a sensing range of 0 – 2000 ppm and
voltage output of 0 to 10 VDC (100 ohm output impedance). The
Pitot Tube sensing device is located in the unit ventilators return
air stream. The optional CO2 sensor is used with the UVC’s
Demand Control Ventilation feature to vary the amount of outside
air based on actual room occupancy. With network applications,
the unit mounted sensor can be overridden by a remote sensor
through the network.
19. Water Out Temperature Sensor (S9): The water out temperature
sensor is factory wired. The sensor must be eld-installed and
insulated (by others) and located on the return connection of the
plate heat exchanger.
20. Water Coil DX Temperature Sensor (S5): The S5 sensor is
factory wired, installed and insulated. It is located on the lower
left refrigerant line of the plate heat exchanger leading to the
expansion valve.
Not all external signal options can be used simultaneously and
may not be available on all software models. Refer to the “UVC
Input and Output Tables” in IM 739 for available options.
NOTICE
Figure 45: Top View - Local User Interface Compartment
9. Fuse(s): Fan motor and controls have the hot line(s) protected by
factory installed cartridge type fuse(s).
10. Control Transformer: 75 VA 24-volt NEC Class 2 transformer
for 24 volt power supply. (Located behind the motor transformer).
11. Outdoor Air/Return Air Damper Actuator (A1): Direct coupled,
oating point (tristate) actuator that spring returns the outdoor air
damper to the closed position upon a loss of power.
12. Low Refrigerant Temperature Sensor (S4): The S4 sensor is
provided on all units with a direct expansion (DX) cooling coil.
It is located on the right hand side of the air coil “u-bend”.
13. Room Temperature Sensor (S1): The unit mounted sensor is
located in the sampling chamber (front, center section) where
room air is continuously drawn through for prompt response
to temperature changes in the room. A Remote Wall Mounted
Temperature Sensor is also available for remote room temperature
sensing. (optional accessory).
14. Discharge Air Temperature Sensor (S2): The sensor is located on
the second fan from the right to sense discharge air temperatures.
Figure 44: MicroTech II Control Boards (with LonWorks
Module Installed)
Plug-in Control Module
Terminal Connections